Permit: T08OT02528

Parcel: 12709012E

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T08OT02528

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/14/2008 FIRE - FINAL Approved
11/05/2008 FIRE - FINAL Denied 1. Need up to date fire sprinkler inspection done last on file 1/13/2006.
2. Need a 5-year alarm check valve inspection.
3. Repair or replace battery back up lighting.
4. Repair or replace exit signs battery back power not working.
5. Replace missing ceiling tiles thought out suite.