Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T08OT02464
Inspection Description - SIGN SHOP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2010 | SIGN SHOP | Approved | IVRS - Inspection :* | |
04/19/2010 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
04/12/2010 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) M/C TO TERMINATE 2) MAINTAIN GTO CLEARANCES TO GROUNDED SURFACES 3) ISOLATE POWER TO SWITCH 4) MARKING LABEL NOT FILLED OUT 5) BOOTS FOR WET LOCATION AND SLEEVING FOR WET LOCATION NEEDED 6) ONLY ONE CONDUCTOR PER TERMINAL SCREW 7) SEAL TIGHT NOT LISTED FOR BURIAL-WHERE IS IT CONNECTED TO ? |