Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2008 | FIRE - FINAL | Approved | ||
| 10/29/2008 | FIRE - FINAL | Denied | Rear exit door needs to be a thumb latch style dead bolt lock. Can not use a double clyinder keyed dead bolt lock. | |
| 10/15/2008 | FIRE - FINAL | Denied | 1. Post address numbers on building per code 12" number. Paperwork given 2. Remove locking hasps from front door only approved locking devices allowed. 3. Extension cords are not allowed as permanent wiring. Remove cords and add outlets to coolers and TV on north wall by front entrance. 4. Repair front exit sign. 5. Outlet cover plate needed on outlet on north wall. 6. Need exit sign for rear exit showing way to rear exit from sales floor. 7. Need to repair or replace exit sign over rear exit door and install back up lighting. 8. Remove slide bolt lock on rear door use only approved locking devices. 9. Cut off 6" bolts that are welded on rear exit door. |