Permit: T08OT02454

Parcel: 12618217A


Addresses:

4221 E 22ND ST #155


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T08OT02454

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/08/2009 FIRE - FINAL Approved
04/30/2009 FIRE - FINAL Denied 1.) Directional signs must be illuminated at all times, internally or externally.
2.) Provivde illuminated directional exit sign or provide an emergency back-up light over the west exit door.
04/09/2009 FIRE - FINAL Denied 1.) Need a copy of the annual sprinkler report
2.) Need a copy of the 5 yr. sprinkler check valve report.
3.) Need panic hardware on the main exit double doors. (Occupancy load exceeds 300)
4.) Lable the riser room "RISER ROOM ".
5.) Lable middle doors "DOOR BLOCKED" on the exterior side of the door.
6.) Secure the compressed gas cylinders.
7.) Provide a directional exit sign indicating the direction to west exit door.
8.) Remove the shelves located in the public restroom, they will obstruct the spray pattern of the sprinkler head.
03/06/2009 FIRE - FINAL Denied Many of the corrections were not made. Items from prior list complied with are #4, 5a, 5b, 11a, 13, 20, 21and # 24. Other corrections required have been added. Numbering continues from prior list.
25.) Must make the SW door on main floor readily accessable for exiting. It is the 2nd. required exit.
26.) Middle double doors must open readily or must remove all hardware. Door must not appear like or resemble a door.
28.) Provide a sign on the exterior side of door reading "DOOR BLOCKED" if removing hardware.
29.) The following items on the list shall be completed by 3/16/09 or proceedings for citation will follow.
Items,1,2,9,10,17,18,22,23 and 26
11/18/2008 FIRE - FINAL Denied Not approved 11/18/08.
1.) Require a lighted exit sign over second exit.
2.) Exit lights burnt out.
a.) Over main exit door.
b.) Over rear exit door. Storage area.
3.) Extension cords for temporary use only. Provide approved permanent power supply for all appliance and fixtures.
4.) Use only approved type plug adaptors.
5.) Cover openings in walls and ceiling:
a.) Throughout ceiling, main floor.
b.) Wall in full bathroom area.
c.) Ceiling in storage area.
6.) Secure gas cylinders.
7.) All permanent electrical wiring shall be installed according to the electrical code.
a.) Water heater room area. Open end wiring
b.) Secure open wiring around ceiling fan, main floor next to money exchange booth.
c.) Splicing of electrical wiring is to be done according to the electrical code. Wiring to ceiling fan, same location.
d.) Exposed wiring in the riser room area.
8.) Cover plates
a.) next to dryer in main storage area.
b.) in "riser room"area.
9.) Accumulation of combustible storge and material in the storage area shall be reduced to minimize fire load.
10.) Provide clear and unobstructed isles in the strorage area.
11.) Require 18 inches of clearance from any sprinkler deflector.
a.) Pinatas
b.) High pile storage.
12.) Need a clear working space around sprinkler valves. Riser room.
13.) Need clear working space around any electrical panel.
14.) Lable riser room door, 'RISER ROOM'. 4 to 6 inch letters.
15.) Portable fire extinguishers are to be serviced and maintained annually or remuved.
16.) Repair emergency back-up lights.
17.) Remove security bar from rear exit door.
18.) Panic hardware is required for all doors in all "A" class occupancy businesses having an occupant load of over 300. Your occupant load is 437.
19.) Double doors to the west are hard to open. Must open readily.
20.) Need plans and permit for addition of the wall creating the small storage area.
21.) Addition of small storage area created a violation with sprinkler head position requirements. You shall provide plans and permits to comply with requirements or remove the wall. Demolition permit required.
22.) Provide annual sprinkler inspection report.
23.) Provide 5 yr. check valve inspection report.
24.) Double-cylinder locks on bathroom doors shall be removed.
10/15/2008 FIRE - FINAL Denied No one on site knows English or where approved plans are, need to have someone on site to talk to and have approved plans on site.