Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2008 | SIGN ELECTRIC | Approved | IVRS - Inspection :* | |
| 11/17/2008 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. A WALKWAY PER 600.21 IS NEEDED 2. A SERVICE LIGHT PER 210.70 IS NEEDED 3. A SWITCH IS NEEDED FOR "OPEN/CLOSED" SIGNS - 600.6 |