Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T08OT02444
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/10/2009 | FIRE - FINAL | Approved | ||
12/17/2008 | FIRE - FINAL | Cancelled | ||
12/16/2008 | FIRE - FINAL | Denied | Remove slide bolt lock from front door. Remove padlock hasp from front door. Need two exits from building Occ load is 83 back door need to open outward. Install exit sign over 2nd exit. (Both 120v and battery back up). Install battery back up lighting. Install thumb latch style dead bolt lock on rear door. |