Permit: T08OT02291

Parcel: 13510150C

Inspection Status: Approved

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
11/21/2008 SIGN SHOP Approved IVRS - Inspection :*
11/14/2008 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SHEETMETAL THREAD SCREWS NOT ALLOWED FOR GROUNDING
2. GROUND SWITCH JUNCTION BOX
3. USE TERMINAL END FOR STRANDED GROUND CONDUCTOR
4. SAM MANUAL CALLS FOR 4" SPACING FROM HEAT PRODUCING COMPONENTS
5. PLEASE PROVIDE ACCESS TO SIGNS OVER ROOF
6. BOND CONDUCTOR TO BE 314 MIN. 600.7 (D)

OK ROOF/DOG HOUSE SIGN
11/13/2008 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
CANCELED