Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2008 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 11/14/2008 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SHEETMETAL THREAD SCREWS NOT ALLOWED FOR GROUNDING 2. GROUND SWITCH JUNCTION BOX 3. USE TERMINAL END FOR STRANDED GROUND CONDUCTOR 4. SAM MANUAL CALLS FOR 4" SPACING FROM HEAT PRODUCING COMPONENTS 5. PLEASE PROVIDE ACCESS TO SIGNS OVER ROOF 6. BOND CONDUCTOR TO BE 314 MIN. 600.7 (D) OK ROOF/DOG HOUSE SIGN |
|
| 11/13/2008 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* CANCELED |