Inspection History Details
Inspection Status: Approved
Inspection History: CERTIFICATE OF OCCUPANCY
Permit Number - T08OT02118
Inspection Description - CERTIFICATE OF OCCUPANCY
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2008 | CERTIFICATE OF OCCUPANCY | Approved | IVRS - Inspection :* | |
| 09/26/2008 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TPRV DISCHARGE TO BE CPVC, COPPER OR GALVANIZED STEEL NOT BLACK FROM OR PVC OR POLYPROPELENE 2. BLANK ALL OPENINGS IN DEAD FRONTS 3. INSTALL MINIMUM 16 GAUGE DEAD FRONT IF HOMEMADE IT MUST BE DEBURRED AND FIT TIGHTLY (1/16" GAP) |
|
| 09/10/2008 | CERTIFICATE OF OCCUPANCY | Not ready for Inspection | IVRS - Inspection :* 1. GFCI RECEPTACLES REQUIRED IN KITCHEN ALONG COUNTER 2. COVER HOLES IN WALLS 3. TPRV DISCHARGE LINE TO TERMINATE @ EXTERIOR OF BUILDING 6" TO 18" ABOVE GRADE 4. REPAIR OR REMOVE WOOD FENCING 5. ANTI-SIPHON DEVICES REQUIRED ON UNCAPPED HOSE BIBS 6. DEAD FRONTS REQUIRED ON ALL SERVICE & SUB-PANELS 7. SECURE ELECTRIC @ NORTH SERVICE PANELS 8. COVER UNUSED OUTLETS |