Permit: T08OT02087

Parcel: 13011270B

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
09/19/2008 FIRE - FINAL Approved Approved 9/19/08.
09/08/2008 FIRE - FINAL Denied 1. Repair or replace exit signs in building both signs need to be internally illuminated, exit sign in warehouse battery back up power failed shall repair.
2. Remove thumb latch dead bolt lock from egress door on southeast corner of building or remove panic hardware device from door and keep thumb dead bolt lock. Can not have both devices on door.
3. Properly cover 110V wiring in closet, any wiring below 7 foot in height shall be protected of damage by covering with sheet rock or install in conduit. Located in lobby closet in basement area.