Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2008 | FIRE - FINAL | Approved | Approved 9/19/08. | |
| 09/08/2008 | FIRE - FINAL | Denied | 1. Repair or replace exit signs in building both signs need to be internally illuminated, exit sign in warehouse battery back up power failed shall repair. 2. Remove thumb latch dead bolt lock from egress door on southeast corner of building or remove panic hardware device from door and keep thumb dead bolt lock. Can not have both devices on door. 3. Properly cover 110V wiring in closet, any wiring below 7 foot in height shall be protected of damage by covering with sheet rock or install in conduit. Located in lobby closet in basement area. |