Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2008 | FIRE - FINAL | Denied | Not approved 9/4/08. 1.) Need illuminated exit signs over both required exits and over door leading from storage area into the main sales floor. 2.) Remove slide-bolt locking device from secondary exit door. 3.) Remove cross-bar locking device from secondary door. 4.) Provide secondary exit door with a thumb-turn lock or other approved locking device. 5.) Cover openings in walls or ceilings in the following areas: a.) front office area. b.) area next to the bathrooms. c.) area around the secondary exit. d.) ceilinga and walls in the main storage area. e.) provide lid covers for scuttle holes X2. 6.) Provide missing cover plates a.) front office area X4 b.) area around bathroom X9 c.) behind front counter. d.) storage area and storage office area. 7.) Open wiring a.) area next to bathroom. b.) backside of wall behind front counter. c.) office area in storage room. |