Inspection History Details
Inspection Status: Denied
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2010 | SIGN SHOP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO WORK PROGRESS-UNECESSARY INSPECTIONS MAY RESULT IN REFEE |
|
| 06/03/2010 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPROT JUNCTION BOXES 2) GROUND JUNCTION BOXES 3) FILL UNUSED OPENING IN RACEWAY-NOT UNUSED FITTING 4) LIGHTS CANNOT BE ON SIGN CIRCUIT 600.5 5) HAVE FLOURESCENT RACEWAY OPEN UP TO INSPECT |