Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T08OT01955

Parcel: 13018001M


Addresses:

3902 E 29TH ST


Inspection Status: Denied

Inspection History: SIGN SHOP

Permit Number - T08OT01955

Inspection Description - SIGN SHOP

Inspection Status - Denied

Date Description Inspector Results Comments
11/30/2010 SIGN SHOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO WORK PROGRESS-UNECESSARY INSPECTIONS MAY RESULT IN REFEE
06/03/2010 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SUPPROT JUNCTION BOXES
2) GROUND JUNCTION BOXES
3) FILL UNUSED OPENING IN RACEWAY-NOT UNUSED FITTING
4) LIGHTS CANNOT BE ON SIGN CIRCUIT 600.5
5) HAVE FLOURESCENT RACEWAY OPEN UP TO INSPECT