Permit: T08OT01936

Parcel: 13314456A

Inspection Status: Cancelled

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
08/21/2008 FIRE - FINAL Cancelled IVRS - RI canceled
08/21/2008 FIRE - FINAL Denied 1.) Need up to date fire sprinkler inspection, this is done yearly last on file 11/27/2003.
2.) Need up to date 5 year alarm check valve inspection, this is done every 5 years. Nothing on file.
3.) Need to replace missing FDC caps on sprinkler connections. Due to duck tape pushed into one of the connections need to make sure no trash or dirt is the connections by have them cleaned out.
4.) Need to remove all 2x4's and all combustibles above ceiling this area is to be non-combustible or add sprinkler coverage above ceiling.