Inspection History Details
Inspection Status: Cancelled
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2008 | FIRE - FINAL | Cancelled | IVRS - RI canceled | |
| 08/21/2008 | FIRE - FINAL | Denied | 1.) Need up to date fire sprinkler inspection, this is done yearly last on file 11/27/2003. 2.) Need up to date 5 year alarm check valve inspection, this is done every 5 years. Nothing on file. 3.) Need to replace missing FDC caps on sprinkler connections. Due to duck tape pushed into one of the connections need to make sure no trash or dirt is the connections by have them cleaned out. 4.) Need to remove all 2x4's and all combustibles above ceiling this area is to be non-combustible or add sprinkler coverage above ceiling. |