Inspection History Details
Inspection Status: Approved
Inspection History: CERTIFICATE OF OCCUPANCY
Permit Number - T08OT01828
Inspection Description - CERTIFICATE OF OCCUPANCY
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/27/2008 | CERTIFICATE OF OCCUPANCY | Approved | IVRS - Inspection :* | |
08/06/2008 | CERTIFICATE OF OCCUPANCY | Not ready for Inspection | IVRS - Inspection :* 1) ANTI SIPHON REQUIRED ON HOSE BIBBS 2) USE PROPER COVERS AT ELECTRIC OUTLETS; SUPPORT CONDUITS OFF ROOF; REMOVE UNUSED WIRING ETC... 3) SUPPORT ALL MECHANICAL RUNS OFF ROOF, REMOVE UNUSED MECH SYSTEMS (WATER HEATER ON ROOF) 4) REPAIR BROKEN GLASS BY DOOR (USE SAFETY GLAZING) 5) LABEL ALL ELECTRIC DISCONNECTS 6) NEED PERMIT FOR MINI SPLIT OR RELOCATE PLUG RECEPTACLE AND ATTACH FACTORY CORD 7) I NEED FLOOR PLAN TO DETERMINE DOOR HARDWARE AND EXIT SIGN REQUIREMENTS 8) DRILL 2" HOLE ON TOP OF 6" RAIN SCUPPERS |
|
08/04/2008 | CERTIFICATE OF OCCUPANCY | Not ready for Inspection | IVRS - Inspection :* 1. INSTALL BACKFLOW PREVENTERS ON EXTERIOR HOSE BIBS 2. INSTALL COVERS ON EXTERIOR ELECTRIC JUNCTION BOXES 3. REMOVE LOOSE WIRING ON WEST EXTERIOR 4. 6" ROOM DRAIN HAS NO SUPPORT OTHER THAN MAKESHIFT CANOPY APPROX. 20' 5. SECURE (CONDUIT TO BLDG. ON TOP OF CANOPY) AND REPAIR CONNECTIONS 6. REMOVE HANGING TEMPORARY WIRING THROUGHOUT INTERIOR 7. REPAIR BROKEN GLASS USE SAFETY GLASS BY DOOR 8. DOOR KNOB TO BE CHANGED OUT AT INTERIOR ENTRY DOOR 9. NEEDS FIRE C OF O A. EXIT SIGNS REQ. B. DOUBLE KEYED KNOBS ON FRENCH DOORS 10. WITHIN 10 DAYS LANDLORD NEEDS TO RESOLVE UNPERMITTED PLUMBING AND ELEC. WORK 11. SPACE SHOULD NOT HAVE BEEN OCCUPIED BEFORE C OF O ISSUED |