Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T08OT01823
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2008 | FIRE - FINAL | Approved | ||
| 08/19/2008 | FIRE - FINAL | Denied | EXIT SIGNS OVER DOORS NOT LIT. | |
| 08/14/2008 | FIRE - FINAL | Denied | EXIT SIGNS NOT LIT. NEED EMERGENCY LIGHTS IN DINING AREAS. NEED PANIC HARDWARE ON TWO EXTERIOR EXITS & ON PATIO GATES ( ACCORDING TO PLAN 2 EXITS ARE REQUIRED FROM PATIO AREA) NO OTHER LOCKS ARE ALLOWED WHERE PANIC HARDWARE IS INSTALLED. HAVE THE HOOD SYSTEM INSPECTED. NEED A SPLASH GUARD BETWEEN THE FRYER & RANGE. NEED A CLASS "K" EXT. |