Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/04/2008 | FIRE - FINAL | Approved | ||
| 07/31/2008 | FIRE - FINAL | Denied | NEED UP TO DATE FIRE SPRINKLER INSPECTION. THIS IS DONE YEARLY LAST INSPECTION ON FILE WAS ON 6/27/2004. NEED UP TO DATE 5 YEAR ALARM CHECK VALVE INSPECTION, NOTHING ON FILE. NEED TO CORRECT SPRINKLER COVERAGE IN NEW HALLWAY. NEED APPROVED PLAN AND PERMIT BEFORE INSATLLATION OF ANY FIRE SPRINKLERS. |