Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T08OT01782
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/07/2008 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
10/06/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USING SERVICE DISCONNECTS AS RACEWAYS FOR BOTH PROTECTED AND UNPROTECTED CONDUCTORS OF DIFFERENT SERVICE LOADS AND SUPPLY SIDE OF SERVICE NOT ALLOWED PER 230 NEC. 2. REPLACE BROKEN RECEPT. COVER ON WEST, OUTSIDE WALL OF MAIN BLD. ALSO, NORTH OUTSIDE WALL, EAST WALL 3. SEPARATE BLD. #2 (CANOPY) STILL HAS OPEN WIRING OWNERS REP. HAS REQUESTED THAT POWER BE RESTORED TO COMPLETE CHECK OUT OF ELEC. EQUIPMENT 4. EXTENDED CORDS TO AC UNITS NOT APPROVED WIRING METHOD |
|
09/17/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WIRING THROUGHOUT BLD. & CARWASH AREA IN NEED OF REPAIR. MISSING COVERS OR PARTS TO VARIOUS EQUIP. EXPOSED WIRING, DBL. LUGGING IN DISCONNECT AT SERVICE AND COOLER DISC. SW 2. RECEPTACLES IN VEHICLE SERVICE AREA WILL NEED TO BE GFI PROTECTED, CHANGE PRIOR TO FINAL USE QUALIFIED OR LICENSED ELECTRICAL CONTR. |