Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2008 | FIRE - FINAL | Approved | ||
| 07/23/2008 | FIRE - FINAL | Denied | Occ load is 65 1. Rear exit door needs to swing outward. 2. Need floor plan showing what rooms are to be used for, can not exit through storage areas. 3. Need floor plan showing proper exiting requirements for occ load over 49. |