Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2009 | FIRE - FINAL | Denied | 1.) Must submit plans to Fire Dept. for approval. | |
| 05/12/2009 | FIRE - FINAL | Not ready for Inspection | Need to have a licensed hood system company to do inspections on hood system. Need to have a report from a licensed company certifying hood extinguisher system for proper coverage and properations. |
|
| 04/07/2009 | FIRE - FINAL | Denied | Item #12 still not in compliance. 1.) Appliances covered (protected) by the hood system must be a minimum 6 inches within the edge of the canopy. 2.) Nozzle piping still needs to be secured. 3.) Re-evaluate nozzle positionaing. 4.) Any alterations made to the hood system or to the appliance line up requires a plan and permit. |
|
| 03/26/2009 | FIRE - FINAL | Denied | The inspection results for this address and for this activity number are the same inspection results as for 248 E. 22nd. St, and activity number T08OT01692. One building, one property, two seperate business addresses and names sharing a common exit. 1.) Emergency back-up light over main door in the restaurant area is burnt out. 2.) Extension cords are for temporary use only. 3.) Cover plate, bar area. 4.) Secondary exit door access, dining area, SE wall, is obstructed with chairs. Must be clear of obstruction at all times. 5.) Provide an exit sign directing to secondary exit door in dining area. 6.) Remove keyed locking device from west exit door in "La Buena" and replace with a thumb-turn lock. 7.) Extension cords can not be placed through the ceiling. Over main exit door in "La Buena" 8.) Emergency back-up lights are burnt out. Tortilla shop. 9.) Cover plate behind counter. Tortilla shop. 10. ) Compressed gas cylinders shall be secured. 11.) Provide illiminated directional exit signs in the following locations: a.) passage door, north side. prep area room. b.) passage door, south side, dishwasher room. c.) 12.) Re-evaluate kitchen hood for : a.) nozzle position b.) lose piping. c.) Missing filter e.) addition of appliance, not protected. 13.) Missing filters for the #2 hood. 14.) Need cover plate behind short range, #2 hood. 15.) Only one locking device allowed per door. Remove one of the locks, flowr tortilla area, west side. 16.) Emergency back-up light, back room, burnt out. 17.) Replace covers for all scuttle holes. 18.) Place a sign on the metal exterior door to storage area that reads "NOT AN EXIT". 19.) Remove pad locks from both walk-in coolers. 20.) Provide a minimum clearance of 24 inches below the ceiling. Over freezer. 21.) Provide a minimum of 36 inches of clear working space infront of an electrical panel. 22.) Re-locate exit sign located over the east exit door in the corn tortilla factory to a lower position so that it can be seen from all locations in the room. 23.) Elecrtical wiring in the water heater shed outside is to be secured and meet electrical code standards. 24.) need cover plates in outside shed area. |