Permit: T08OT01525

Parcel: 11005319A

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
09/24/2008 FIRE - FINAL Approved
07/02/2008 FIRE - FINAL Denied Not approved 7/2/08.
1.) Main exit door for each suite needs signage over door reading " DOOR TO REMAIN UNLOCKED WHILE BUILDING IS OCCUPIED".
2.) Extension cords to be used for temporary use only.
3.) Remove panic push bars from all exit doors provided with this hardware.
4.) Maintain unobstructed pathway to all exits at all times.
5.) Missing plugs from electrical panel located in server room.
6.) Maintain clear pathway 36 in. minimum to all electrical panels.
7.) Lable door to the electrical room, " ELECTRICAL".
8.) Portable extinguishers are past due for inspection.
9.) Provide Exit signs for the following areas:
a.) Main exit doors in all suites.
b.) South and West exit doors.
c.) Directional, indicating pathway to exits not readily visible from
certain areas in the building.