Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/22/2008 | SIGN ELECTRIC | Approved | IVRS - Inspection :* | |
| 10/20/2008 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CANNOT USE SHEETMETAL THREAD SCREW - 250.8 2. BOND POWER SUPPLY ENCLOSURE |
|
| 10/17/2008 | SIGN ELECTRIC | Cancelled | IVRS - RI canceled | |
| 10/14/2008 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ISOLATE POWER TO SWITCH ON SIGN 2. BOND LED LETTERS 600.7 3. ANCHORS NOT HOLDING LETTER TO WALL 4. PROVIDE WALKWAY PER 600.22 5. A SERVICE LIGHT IS NEEDED - 210.70 6. SUPPORT 3/8 FLEX 12" & 6' 7. NEED SIGN PAPERWORK |