Permit: T08OT01398

Parcel: 14029003H

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
10/28/2008 FIRE - FINAL Approved
09/02/2008 FIRE - FINAL Denied Need to correct sprinkler coverage in the following areas:
1. Sterilization room need to add sprinkler heads.
2. Room #178 correct sprinkler coverage.
3. Medical director offices correct sprinkler coverage.
4. Room #105 correct sprinkler coverage.
5. Have sprinkler coverage in copy room check by sprinkler contractor.
6. Change 1 painted sprinkler head outside by front entrance door.
7. Change exit sign direction by rooms 180 and 179 can not have exiting going through storage rooms.