Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/08/2008 |
FIRE - FINAL |
|
Approved |
|
| 07/03/2008 |
FIRE - FINAL |
|
Denied |
ELECT. RECEPTACLE UNDER HOOD NOT SHUTTING DOWN. |
| 06/10/2008 |
FIRE - FINAL |
|
Denied |
NEED MECH. INSP. NEED ACCEPTANCE TEST OF HOOD SYSTEM |
| 05/22/2008 |
FIRE - FINAL |
|
Denied |
PUT SIGN OVER EXIT STATING "THIS DOOR TO REMAIN UNLOCKED WHILE THE BUILDING IS OCCUPIED". REMOVE EXTENSION CORDS. NEED TO PLUG APPLIANCES INTO ELECT. WALL OUTLET. NEED A PORTABLE CLASS "K" EXTINGUISHER FOR COOKING APPLIANCES. A PLAN & PERMIT IS REQUIRED FOR PROPER EXTINGUISHING COVERAGE FOR THE HOOD SYSTEM & APPLIANCES. MOVE PULL STATION 10' TO 20' FROM THE HOOD SYSTEM. |