Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T08OT01207
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2008 | FIRE - FINAL | Approved | ||
| 07/03/2008 | FIRE - FINAL | Denied | ELECT. RECEPTACLE UNDER HOOD NOT SHUTTING DOWN. | |
| 06/10/2008 | FIRE - FINAL | Denied | NEED MECH. INSP. NEED ACCEPTANCE TEST OF HOOD SYSTEM | |
| 05/22/2008 | FIRE - FINAL | Denied | PUT SIGN OVER EXIT STATING "THIS DOOR TO REMAIN UNLOCKED WHILE THE BUILDING IS OCCUPIED". REMOVE EXTENSION CORDS. NEED TO PLUG APPLIANCES INTO ELECT. WALL OUTLET. NEED A PORTABLE CLASS "K" EXTINGUISHER FOR COOKING APPLIANCES. A PLAN & PERMIT IS REQUIRED FOR PROPER EXTINGUISHING COVERAGE FOR THE HOOD SYSTEM & APPLIANCES. MOVE PULL STATION 10' TO 20' FROM THE HOOD SYSTEM. |