Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T08OT01177
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/25/2008 | FIRE - FINAL | Approved | ||
08/11/2008 | FIRE - FINAL | Denied | 1.) Need up to date fire sprinkler inspection, last inspection on file dated 02/2004. This inspection is to be done yearly. 2.) Need up to date 5 year fire alarm check valve inspection, nothing on file. 3.) North bathroom sprinkler heads to close together need to correct coverage. |
|
08/07/2008 | FIRE - FINAL | Denied | LOCKED UNABLE TO MAKE ENTRY |