Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T08OT01106

Parcel: 12112365A


Addresses:

5146 E PIMA ST

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
05/19/2010 FIRE - FINAL Approved
12/24/2009 FIRE - FINAL Denied Not approved 12/24/09
1.) Provide emercency back-up lighting to illuminate directional exit sign when electrical power for building is lost.
2. Existing emergency back-up lights are too dim. Lights must been bright enough to illuminate the exit pass.
09/10/2009 FIRE - FINAL Denied Corrections still required for following items off previous violations list;
Items 1,2,4,5,9,10.11 and 12.
06/03/2009 FIRE - FINAL Denied Not approved 5/2/09.
1.) Exit signs over both exit doors located in the vestibule area are burnt out.
2.) Provide a readily visable sign reading ,"NOT AN EXIT" on the inside portion of the front ,west door that leads out to the vestibule area.
3.) Check and update all portable fire extinguishers for annuual servicing (6 counted).
4.) Extention cords are to be for temporary use only not as a substitute for permamnent wiring.
a.) parts and sales counter
b.) storage area./inventory control.
5.) Provide directional exit signs in the Safe/Clothing area. Signs must be illuminated by internal or external lighting at all times.
6.) Provide a directional exit sign with an arrow, on the wall located directly outside of the rear exit door.
7.) Must install a door self- closer on the door of the storage room located outside of the rear exit door.
8.) Pad locking devices are prohibited.
a.) remove pad locking device from outside storage room door.
b.) remove padlock from Sprinkler Riser Room door.
9.) Emergency back-up lights are burnt out.
10.) Provide emergency back-up lighting for the basement area.
11.) Lable door leading to the basement area, "BASEMENT" and "RISER ROOM"
12.) All required exit doors and doors that are part of the exiting path must open in the direction of egress.
02/19/2009 FIRE - FINAL Cancelled Plans not required as per Building Dept. and confirmed by DMann.