Inspection History Details
Inspection Status: Approved
Inspection History: CERTIFICATE OF OCCUPANCY
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2008 | CERTIFICATE OF OCCUPANCY | Approved | IVRS - Inspection :* | |
| 10/01/2008 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* ITEM 4 NOT DONE - MAINTAIN & SUPPORT DUCTING IN SEWING ROOM ITEM 6 NOT DONE - BLOCK WAS NOT RE-LAYED NOR GROUTED IT WAS SIMPLY PUSHED INTO PLACE AND REPOINTED (BADLY) ON THE INSIDE |
|
| 06/30/2008 | CERTIFICATE OF OCCUPANCY | Denied | 1) ADDRESS DISPLAY TO BE 12" MINIMUM HEIGHT. 2) SIGN OVER FRONT DOOR "THIS DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS." 3) 3' WORKING SPACE REQUIRED IN FRONT OF SERVICE PANELS. 4) DUCTING MUST BE PROPERLY MAINTAINED & SUPPORTED IN SEWING ROOM. 5) ROOF APPEARS TO BE LEAKING (MOISTURE FOUND IN ATTIC). 6) EAST WALL HAS EXTENSIVE DAMAGE TO MASONRY. IT MUST BE EVALUATED BY A QUALIFIED ENGINEER AND PROPERLY REPAIRED. 7) WOODEN STRUCTURE ALONG SOUTH PROPERTY LINE MUST BE REMOVED OR BROUGHT UP TO CODE. 8) ALL EXTERIOR HOSE BIBBX REQUIRE ANTI-SIPHON DEVICES. 9) EXTERIOR OUTLETS REQUIRE WATERPROOF COVERS. 10) MEZZANNINE IN SHOP APPEARS TO HAVE OVER-SPANNED JOISTS WITHOUT PROPER SUPPORTS. I WILL REVIEW THIS ITEM IN MORE DETAIL FOR ALLOWABLE LOADS IN THIS TYPE OF CONSTRUCTION. IT MAY HOWEVER BE REQUIRED TO BE REMOVED. 11) ROMES WIRING IN SHOP MUST BE PROTECTED BELOW 7' AND PROPERLY SUPPORTED EVERYWHERE. 12) YOU MAY NOT HAVE A SERVICE SINK BELOW YOUR ELECTRIC PANEL IN SHOP. |