Inspection History: SIGN ELECTRIC
Permit Number - T08OT00807
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/11/2008 | SIGN ELECTRIC | Approved | IVRS - Inspection :* | |
06/04/2008 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT MC CABLE WITHIN 12" OF BOX 2. PROPERLY SUPPORT FLEX 3. MAINTAIN GTO CLEARANCE 4. USE APPROPRIATE HARDWARE NOT DRYWALL SCREWS TO MOUNT LETTERS |