Permit: T08OT00705

Parcel: 99999999A

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Permit Number - T08OT00705

Inspection Description - SIGN ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
10/30/2008 SIGN ELECTRIC Approved IVRS - Inspection :*
10/09/2008 SIGN ELECTRIC Partial Approval IVRS - Inspection :*
1) OK PLAN REVISIONS
10/06/2008 SIGN ELECTRIC Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
"C-1", "C-3", "C-5"

1. A GROUNDING ELECTRODE SYSTEM OF 2KVA TRANSFORMER IS NEEDED.
2. ONLY ONE CONDUCTOR PER LUG TERMINATION
3. BOND BUSHINGS NEEDED 250.97
4. SPLICES TO BE FOR WET LOCATION
5. SPLIT BOLTS LISTED FOR (2) TWO CONDUCTORS A RUN &
A TAP ONLY
6. LABEL DISCONNECTING MEANS
7. SIGN NOT TO BE ENERGIZED UNTIL PASSED FINAL INSPECTION
8. PLANS DO NOT HAVE AN ELECTRIC DETAIL
09/24/2008 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection :*
CANCELED