Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/30/2008 | SIGN ELECTRIC | Approved | IVRS - Inspection :* | |
10/09/2008 | SIGN ELECTRIC | Partial Approval | IVRS - Inspection :* 1) OK PLAN REVISIONS |
|
10/06/2008 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* "C-1", "C-3", "C-5" 1. A GROUNDING ELECTRODE SYSTEM OF 2KVA TRANSFORMER IS NEEDED. 2. ONLY ONE CONDUCTOR PER LUG TERMINATION 3. BOND BUSHINGS NEEDED 250.97 4. SPLICES TO BE FOR WET LOCATION 5. SPLIT BOLTS LISTED FOR (2) TWO CONDUCTORS A RUN & A TAP ONLY 6. LABEL DISCONNECTING MEANS 7. SIGN NOT TO BE ENERGIZED UNTIL PASSED FINAL INSPECTION 8. PLANS DO NOT HAVE AN ELECTRIC DETAIL |
|
09/24/2008 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* CANCELED |