Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2009 | FIRE - FINAL | Denied | Need permit for outside metal shed. 2.) Need confirmation of approval from Building Official reguarding addition of seperation wall in warehouse area. |
|
| 09/17/2009 | FIRE - FINAL | Denied | Only items # 4 and # 5 from the previous list have been corrected. Additional items have been added to the list of corrections required. 1.) Need an exit sign over main exit door. Main lobby. 2.) All exit signs must be illuminated at all times. Exit signs are burnt out. 3.) Cover plate . East wall main floor. 4.) Plans and permits required for addition of wall seprating warehouse floor area. 5.) Plans and permits for the large metal storage shed outside, east end of property. 6.) Metal roll-up door, north end, is damaged. Must repair guide track and certify that the door is operational. Also evaluate the damaged portion on the upper section of door. 7.) Reposition key lock on door between main lobby and east end access to warehouse area. |
|
| 03/28/2008 | FIRE - FINAL | Denied | Original building, non-sprinklered portion: 1.) loft area over offices, fire wall seperation is breached. 2.) open wiring, same area, loft. 3.) exit light over west exit door is burnt out. 4.) portable extinguishers are past due for servicing. 5.) remove all stored material from under stairway. Sprinklered areas. 1.) holes in dry wall, south end. 2.) large ceiling fan south end is obstructing sprinkler head. 3.) breach in masonary wall between between sprinklered and non-sprinklered building. 4.) portable extinguishers past due for servicing. 5.) small room addition containing monitoring equipment requires sprinkler protection. Permit required. NW area of floor. 6.) breach in fire seperation wall, same room. 7.) exposed wring NW area nain floor. 8.) exposed wiring N wall. 9.) provide/repair door knob for bathroom. 10.) opening in walss and ceiling in loft area over bathroom. 11.) Provide permits for for additions or alteration made to the |