Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2008 | SIGN ELECTRIC | Approved | IVRS - Inspection :* | |
| 09/16/2008 | SIGN ELECTRIC | Partial Approval | IVRS - Inspection :* FINISH #3 OF PREVIOUS INSPECTION |
|
| 08/22/2008 | SIGN ELECTRIC | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* NO WORK PROGRESS |
|
| 07/23/2008 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. LABEL SIGN CIRCUITS AT PANEL - IS CIRCUIT AS PER 600.5? 2. FILL UNUSED OPENINGS IN BOXES 3. USE APPROVED AND LISTED BOX OPENINGS 4. GROUND JUNCTION BOXES AND USE APPROVED METHODS 5. SUPPORT CONDUITS AS PER CODE 3' & 10' |
|
| 06/02/2008 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* CANCELED -- WAITING ON UL INSPECTION |
|
| 05/01/2008 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* JUST BRAKES - SOUTH: 1. SIGN DOES NOT MEET STANDARDS FOR SIGNS A FIELD EVALUATION IS NEEDED 2. ISOLATE POWER TO SWITCH AS STAMPED ON PLANS CABINET - EAST: 1. ISOLATE POWER TO SWITCH 1. NO POWER TO SIGNS AT THIS TIME |
|
| 04/29/2008 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO PLANS OR PERMITS 2. HAVE SIGN OPEN TO INSPECT |