Permit: T08OT00669

Parcel: 13705507B

Inspection Status: Approved

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
06/10/2008 SIGN SHOP Approved IVRS - Inspection :*
05/22/2008 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) USE APPROVED GROUND DEVICES FOR FITTINGS AT LEXAN
2) MARKING LABELS ARE NEEDED 600.4
3) A SERVICE LIGHT IS NEEDED 210.70
4) USE APPROVED FITTINGS WITH M/C
5) STRAP FLEX LONGER THAN 4' 4'+12"
6) TIGHTEN LOOSE FITTINGS
7) LOCK OUTS NEEDED FOR SWITCHES 600.6
8) A WALK WAY IS NEEDED 600.21