Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/10/2008 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 05/22/2008 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) USE APPROVED GROUND DEVICES FOR FITTINGS AT LEXAN 2) MARKING LABELS ARE NEEDED 600.4 3) A SERVICE LIGHT IS NEEDED 210.70 4) USE APPROVED FITTINGS WITH M/C 5) STRAP FLEX LONGER THAN 4' 4'+12" 6) TIGHTEN LOOSE FITTINGS 7) LOCK OUTS NEEDED FOR SWITCHES 600.6 8) A WALK WAY IS NEEDED 600.21 |