Permit: T08OT00622

Parcel: 125072170


Addresses:

2345 E 6TH ST


Inspection Status: Denied

Inspection History: CERTIFICATE OF OCCUPANCY

Permit Number - T08OT00622

Inspection Description - CERTIFICATE OF OCCUPANCY

Inspection Status - Denied

Date Description Inspector Results Comments
07/28/2008 CERTIFICATE OF OCCUPANCY Denied IVRS - Inspection :
See detailed listing on site.| 999*
HOME MUST BE IN GOOD REPAIR -
INCLUDING COUNTERS AND CARPET

1. INSTALL PROPER DEAD FRONT @ SERVICE PANEL
2. WIRE LIGHT IN COURTYARD PER NEC
3. LEAKING ROOF @ LAUNDRY
4. IMPROPER WIRING @ OUTLET ABOVE LAUNDRY SINK
5. UNCOVER NEW PLUMBING UNDER LAUNDRY CABINET FOR INSPECTION
6. ALL BEDROOMS REQUIRE PERMANENT HEATING AND COOLING
7. YOU CANNOT USE EXTENSION CORDS TO POWER APPLIANCES (STOVE)
8. FIX LOOSE FLOOR BOARDS
9. WEATHERPROOF ALL DOORS AND WINDOWS
10. FIX ALL DOOR KNOBS
11. REMOVE LOFT IN REAR UNIT
12. PROPERLY SUPPORT DRAIN @ REAR UNIT
13. REPAIR DRAIN @ REAR UNIT
14. SAFETY GLAZING REQUIRED INDOORS
07/23/2008 CERTIFICATE OF OCCUPANCY Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE ACCESS INTO BUILDING
2. HOUSE AND GROUNDS MUST BE IN GOOD REPAIR
A. WATER HEATER HAS NO FLUE OR DOOR FOR ENCLOSURE
B. FLEX CONNECTOR NOT ALLOWED @ GAS METER
C. WINDOW PANES BROKEN
D. ELECTRIC DISCONNECTS NOT LABELED
E. ILLEGAL LOFT IN REAR UNIT
F. UNSUPPORTED CONDUITS, PIPES, ETC.
3. THIS IS NOT A COMPLETE LIST