Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2008 | FIRE - FINAL | Approved | ||
| 05/02/2008 | FIRE - FINAL | Denied | Not approved 5/2/08. 1.) Submit updated plans. 2.) Require building permit for wall addition. 3.) Provide annual sprinkler report. 4.) Provide 5 year sprinkler alarm check valve inspection report. 5.) Lable riser room door "RISER ROOM'. 6.) Thumb-turn latch on SW exit door is hard to turn. 7.) Door knob hardware is not secure. |
|
| 04/07/2008 | FIRE - FINAL | Denied | 1.) Plans do not reflect what is on site, need to up date plans. 2.) Need up to date fire sprinkler inspection, last on file shows 9/13/03. This is to be done yearly. 3.) Need a 5 year fire sprinkler alarm check valve inspection done. 4.) Need to install blanks in electrical panels in warehouse north wall and in the middle. 5.) Sprinkler heads to close together in women's bathroom. 6.) Replace or repair sprinkler heads on south side patio cover. 7.) Replace clear glass on sprinkler shut off (OS&Y) outside front, painted over. 8.) Remove security bar doors on all egress doors in warehouse and front door. 9.) Install back up lighting throughout warehouse and offices. |