Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2008 | FIRE - FINAL | Approved | PER INSP COPY | |
| 04/17/2008 | FIRE - FINAL | Denied | REMOVE PADLOCK SLIDE BOLT FROM EXIT DOOR. (SOUTHWEST END) ONLY USE APPROVED LOCKING DEVICES. LABEL ABOVE DOOR INSIDE THE FOLLOWING "THIS DOOR TO REMAIN UNLOCKED WHEN BUILIDNG IS OCCUPIED". SIGN SHALL BE 1 INCH HIGH LETTERS ON A CONTRASTING BACKGROUND. (NORTHEST END) |
|
| 04/17/2008 | FIRE - FINAL | Denied | REMOVE PADLOCK SLIDE BOLT FROM EXIT DOOR (SOUTHWEST END) ONLY USE APPROVED LOCKING DEVICES. LABEL ABOVE DOOR INSIDE THE WORDING "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED". SIGN SHALL BE 1 INCH HIGH LETTERS ON A CONTRASTING BACKGROUND (NORTHEAST END). |
|
| 02/26/2008 | FIRE - FINAL | Denied | 1. ADDRESS NUMBERS CAN NOT BE PAINTED (paperwork given again) 2. OUTSIDE MAIN BOX NEXT TO METER NEEDS INSIDE PANEL COVER 3. CUT TREE BACK FROMPWER WIRES |
|
| 02/21/2008 | FIRE - FINAL | Denied | 1. Need address numbers posted on building per code, paperwork given. 2. All outside wiring needs to be weather proof - lights, box next to main meter. 3. All wiring going through walls needs to be protected per code. Replace plastic conduit on walls with proper conduit or remove all together. 4. Wiring inside building needs to be up to code. Need cover plates on outlets and switches, need to replace broken outlets. 5. All exposed wiring needs to be installed in conduit. 6. Cut tree back from main power lines. 7. Remove outlet on front of building outside or install properly, can not run wiring without protection of conduit. |