Permit: T08OT00400

Parcel: 120071290


Addresses:

4026 S 6TH AV

Inspection Status: Approved

Inspection History: CERTIFICATE OF OCCUPANCY

Date Description Inspector Results Comments
05/23/2008 CERTIFICATE OF OCCUPANCY Approved PER INSP COPY
04/17/2008 CERTIFICATE OF OCCUPANCY Denied IVRS - Inspection :
See detailed listing on site.| 999*
A. THIS MUST MATCH APPROVED PLANS
B. FURTHER FAILED INSPECTIONS WILL RESULT IN REINSPECTION FEES

1. NO PLANS OR PERMITS ON SITE
2. DOUBLE LUGGED AND OVERFUSED CIRCUITS IN SUB-PANELS
3. LAUNDRY RISER TO BE MIN. 18" AND MAX. 30" LONG
4. SEE #4 FROM 2/20/08, INTERIOR HOSE BIBS MUST ALSO BE PROTECTED
5. NO ACCESS TO OFFICE AREA
6. SEE #5 FROM 2/27/08
02/27/2008 CERTIFICATE OF OCCUPANCY Not ready for Inspection IVRS - Inspection :*
1. SEE #1 FROM 2/20/08
2. SEE #3 FROM 2/20/08
A. DEAD FRONTS
B. OUTDOOR GFCI OUTLETS & COVERS FOR OUTLETS
3. SEE #4 FROM 2/20/08
4. SEE #5 FROM 2/20/08
5. EXIT DOOR & WINDOWS IN OFFICE AREA MUST BE REPAIRED
02/26/2008 CERTIFICATE OF OCCUPANCY Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/20/2008 CERTIFICATE OF OCCUPANCY Not ready for Inspection IVRS - Inspection :*
1. POST 12" ADDRESS DISPLAY
2. EXTERIOR LIGHTS MUST BE LISTED FOR OUTDOOR USE AND PROPERLY WIRED
3. TERMINATE ELECTRIC WIRES INSIDE PROPER BOX
ALL ELECTRIC MUST BE IN GOOD REPAIR
4. ANTI-SIPHON DEVICES REQUIRED ON HOSE BIBBS
5. REPAIR WINDOWS AND WALL OPENINGS
6. INSTALL SERVICE SINK OR CAP DRAIN LINE
7. CAULK TOILET @ FLOOR