Inspection History Details
Inspection Status: Approved
Inspection History: CERTIFICATE OF OCCUPANCY
Permit Number - T08OT00346
Inspection Description - CERTIFICATE OF OCCUPANCY
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/11/2008 | CERTIFICATE OF OCCUPANCY | Approved | ||
06/20/2008 | CERTIFICATE OF OCCUPANCY | Partial Approval | PREVIOUS CORRECTION ITEMS OK. THE ONLY OUTSTANDING ISSUE IS THE WALK-IN COOLER LOCATION WHICH IS IN VIOLATION OF THE LUC. NO BUILDING CODE VIOLATIONS AT THIS TIME | |
03/25/2008 | CERTIFICATE OF OCCUPANCY | Not ready for Inspection | IVRS - Inspection :* CHANGE C OF O TO F-1/M OCC. LOAD 22 1. PLEASE SHOW KITCHEN FIXTURES ON FLOOR PLAN 2. HAND SINK IN KITCHEN REQUIRES VENT ON TRAP ARM 3. CAP ALL UNUSED DRAIN CONNECTIONS INSIDE & IN YARD 4. INSTALL ANTI-SIPHON DEVICES ON ALL HOSE BIBS 5. USE WATERPROOF COVERS ON ALL EXTERIOR PLUG RECEPTACLES 6. YOUR ELECTRIC PANEL HAS A 15A & 20A BREAKER IDENTIFIED AS FEEDING A SUB-PANEL HAVE A QUALIFIED ELECTRICIAN GO THROUGH YOUR PANEL AND SUB-PANELS AND MAKE ANY CODE REQUIRED CORRECTIONS 7. REMOVE IMPROPERLY WIRED OUTLETS IN COURTYARD STORAGE ROOM |
|
03/13/2008 | CERTIFICATE OF OCCUPANCY | Not ready for Inspection | IVRS - Inspection :* NEED APPROVED PLAN ON SITE |