Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2008 | SIGN SHOP | Approved | IVRS - Inspection :* OK SIGN BUILDING ELECTRICAL INSPECTOR TO CHECK CONDUIT BETWEEN BOXES |
|
| 03/27/2008 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. A MARKING LABEL IS NEEDED 600.4 2. GREEN GROUNDING CONDUCTOR TO BE ENTIRE LENGTH 250.119 3. TIGHTEN GROUND SCREW IN JUNCTION BOX 4. SWITCH TO BE LOCKABLE 5. MAINTAIN GTO CLEARANCES |