Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T08OT00283

Parcel: 115080760


Addresses:

1248 N STONE AV

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
06/03/2008 FIRE - FINAL Approved
03/19/2008 FIRE - FINAL Not ready for Inspection 1.) Storage room on north side of building by stone road not on plans need to have plans reflect what is on site.
All other problems noticed where fixed
02/12/2008 FIRE - FINAL Denied 1.) Storage room on north side of building by stone road not on plans need to have plans reflect what is on site.
2.) Wiring on north side coming from storage room needs to be in conduit and weather proof.
3.) Lighting and outlets front driveway not weather proof (stairs-soda mech. and flood lights)
4.) Exits signs on bldg. 1 & 2 2nd floor repair battery back.
5.) Replace missing exit by stairs bldg. 2 2nd floor eastside.
6.) In hot water heater room bldg. 2 replace missing electrical cover for main panel.
7.) In hot water heater rooms bldg. 1 & 2 repair switch behind water heaters.
8.) Pool gates shall be self-closing and latching.
9.) Repair outlets behind washer and dryer in pool area.