Permit: T08OT00116

Parcel: 13613001W

Inspection Status: Approved

Inspection History: SIGN SHOP

Permit Number - T08OT00116

Inspection Description - SIGN SHOP

Inspection Status - Approved

Date Description Inspector Results Comments
03/24/2008 SIGN SHOP Approved IVRS - Inspection :*
03/18/2008 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SIGN CIRCUIT TO BE AS PER 600.5
2. A EQUIPMENT GROUNDING CONDUCTOR IS NEEDED - RACEWAY CANNOT BE THE CONDUCTOR
3. BOX OVERFILLED
4. SUPPORT MC CABLES AS PER CODES
5. MAINTAIN GTO CLEARANCES FROM GROUNDED SURFACES
6. MC CABLE TO TERMINATE

OK MENU BOARD
03/14/2008 SIGN SHOP Not ready for Inspection IVRS - Inspection :*