Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ROOF UNIT 100,000 65,000-RANGE 40,000-H20 HTR ------------------------ 205,000 = APPROX 182 CU. FT PER HR 70'=127 DELIVERY. MAIN GAS LINE NOT LARGE ENOUGH 2) H20 HTR REMOVE TAPE AT SINGLE WALL TO DBL WALL, EXTEND T & P LINE |