Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/03/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 01/14/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ISOLATE DISCHARGE LINE FROM SCRAPING ON COIL KNOCKOUT. EXTEND FURNACE VENT 3' ABOVE COMBUSTION AIR INTAKE. 2. PROVIDE A PERMIT FOR NEW WATER HEATER - 3/4" GAS PIPE FOR 180,000 BTU WATER HEATER & 80,000 BTU FURNACE NOT ADEQUATE 3. T&P DRAIN CANNOT HAVE FLEX COPPER & MUST SLOPE DOWNHILL TO DAYLIGHT |