Permit: T08ME00686

Parcel: 133384140

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/23/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
01/16/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECONDARY OVERFLOW SENSOR MUST BE CONNECTED TO THE OUTLET ON EVAP. COIL, NOT IN THE PRIMARY DRAIN LINE
SOLDER JOINT ON 3/8" CONDENSATE LINE ON ROOF. TAPE BOTH ENDS OF THE WHITE WIRE WITH BLACK TAPE.
12/05/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TAPE WHITE WIRE USED FOR POWER BLACK
2) CONDENSATE PUMP NOT ALLOWED IN RETURN AIR PLENIUM