Permit: T08ME00684

Parcel: 116130970

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/22/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
01/13/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
01/12/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DUCT EXPOSED TO OUTSIDE TEMP MUST BE
INSULATED TO R-8
2. REMOVE ALL FOIL TAPE FROM FLUE PIPING
3. SINGLE WALL JOINTS MUST TELESCOPE MIN. 1" IF AVAILABLE
4. FILTER ACCESS DOOR DOES NOT OPEN
5. PROVIDE MAX. 1/4" BIRD SCREEN AT COMBUSTION
AIR INLET