Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/13/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/12/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DUCT EXPOSED TO OUTSIDE TEMP MUST BE INSULATED TO R-8 2. REMOVE ALL FOIL TAPE FROM FLUE PIPING 3. SINGLE WALL JOINTS MUST TELESCOPE MIN. 1" IF AVAILABLE 4. FILTER ACCESS DOOR DOES NOT OPEN 5. PROVIDE MAX. 1/4" BIRD SCREEN AT COMBUSTION AIR INLET |