Permit: T08ME00680

Parcel: 13314236C


Addresses:

7083 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/01/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
11/26/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MARK UNIT DATA PLATE W/PROPER
HEAT STRIP & FUSE ACCORDINGLY
2. 45 AMP. FUSES WILL NOT WORK WITH THIS UNIT
3. LABEL THE UNIT WITH THE ADDRESS
4. PAINT ALL EXPOSED PVC W/LATEX PAINT
5. PROVIDE A MIN. 1/8" PER FT. SLOPE ON CONDENSATE PIPING