Permit: T08ME00672

Parcel: 133351380


Addresses:

601 N KEEN PL

Inspection Status: Not Applicable

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
12/19/2008 MECHANICAL - INTERMEDIATE Not Applicable
12/12/2008 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ONE PRESENT AT 10:30 AM-RANG BELL
2) PLEASE RE-CALL
11/25/2008 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) NO ACCESS 11:07 AM
2) RECALL INSPECTION
11/19/2008 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DRIP LEG REQUIRED ON WATER HEATER GAS
2) T/P LINE MUST BE HARD PIPED AND REAR DOWN HILL. A PAN CAN BE USED
3) LEAK AT WATER HEATER HOT WATER FLEX
4) CONDENSATE DRAIN CANNOT ENTER PLUMBING VENT-RUN OFF ROOF
ELECTRIC:
5) GET PERMIT FOR PANEL AND CALL FOR INSPECTION
6) BOND GAS LINE
7) G-2411.1 GROUND WIRE GOES UNDER ACORN CLAMP OPPOSITE BOLT