Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/28/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 01/22/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE ALL FOIL TAPE FROM VENT CONNECTOR TO EXPOSE FITTINGS 2. BE SURE ALL FITTINGS ARE NOT UPSIDE DOWN 3. TAPE NOT REQUIRED 4. INSULATE ALL BARE SHEETMETAL SUPPLY DUCT IN FURNACE CLOSET 5. ROMEX CONNECTOR NOT TIGHTENED ONTO POWER CORD 6. CORD HAS EXPOSED WIRES |