Permit: T08ME00526

Parcel: 140160890


Addresses:

1750 E NEVADA ST


Inspection Status: Not ready for Inspection

Inspection History: MECHANICAL - FINAL

Permit Number - T08ME00526

Inspection Description - MECHANICAL - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
08/27/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) RAFTERS RUN EAST/WEST CHANGE SKID DIRECTION, SHIM UNDER UNIT TO KEEP FROM ROCKING
2) PLUG HOLES IN DISCONNECT, SCREW BOX TO STRAP
3) NEED NO LUX ON AL. CONDUCTORS
4) VENT P-TRAP ON CONDENSATE
5) REMOVE TAPE SINGLE TO DBL WALL