Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T08ME00524
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 01/22/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOBODY HOME |
|
| 01/14/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. STRANDS CANNOT BE TRIMMED OFF OF A CONDUCTOR TO MAKE IT FIT INTO A LUG. 2. REDO GROUND & LINE VOLTAGE CONDUCTORS TO FIT PROPERLY. 3. YOU CAN USE #8 ALUM. FOR THE GROUND AND WIRE NUT TO EXISTING GROUND CONDUCTOR |
|
| 09/22/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WIRE SIZE FROM PANEL TO DISCONNECT 2) PROPER GROUND FROM FUSE DISCONNECT 3) MARK FAN UNIT FOR MAX DISCONNECT 4) PROPERLY MARK AND LABEL SERVICE PANEL |