Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T08ME00519
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
10/01/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DATA PLATE ON UNIT STILL NOT IDENTIFIED IN REFERENCE TO HEAT STRIP 2. CORRECTIONS DATED 9/4/08 UNDER OTHER ACTIVITY NUMBER. |
|
09/29/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
09/22/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT FLEX CONDUIT OFF OF ROOF 2. DATA PLATE NOT IDENTIFIED |
|
09/19/2008 | MECHANICAL - FINAL | Cancelled | IVRS - RI canceled | |
09/04/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE AIR BALANCE REPORT 2. DUCTS TO BE HUNG WITH STRAPS LISTED ON GENERAL NOTE 3 3. COFFEE ROASTER DUCT NOT INSTALLED 4. PROVIDE MANUFACTURES INSTALLATION INSTRUCTIONS ON COFFEE ROASTER FLUE PIPING, PIPING WILL NOT BE APPROVED WITHOUT INSTRUCTIONS 5. PROVIDE CLEANOUTS IN COFFEE ROASTER FLUE/VENT PIPING 6. PROVIEE PROPER DESCRIPTION OF WORK |