Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 08/23/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) 1/2" GAS PIPE NOT ADEQUATE FOR 96,000 BTU 70' FROM METER 2) CONTINUE 3/4" PIPE OVER TO CONNECTION TO FURNACE 3) SUPPORT PVC ON ROOF EVERY 4' AND PAINT WITH LATEX PAINT 4) SECURE DRAIN LINE TO SIDE WALL AND TERMINATE WITH AN ELBOW AND NIPPLE 5) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF |