Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) ALL ITEMS CALLED OUT OK AT THIS TIME 2) NEED TO INSULATE DUCT TO A MIN R.8/SEAL ALL JOINTS |
|
| 07/02/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED ACCESS INTO HOUSE TO CHECK JUNCTION BOX IN ATTIC 2) NO ONE HOME, NO NUMBER LEFT TO CALL |
|
| 06/13/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO RE-IDENTIFY NUETRAL BEING USED AS AN UNGROUNDED CONDUCTOR 2) WRONG FUSE IN DISCONNECT BOX FOR A/C, S/B 20 AMP MAX PER LISTING ON UNIT 3) NEED TO LEVEL A/C UNIT 4) NEED TO SUPPORT JUNCTION BOX IN ATTIC AND SECURE CONDUITS 5) NEED TO WATER PROOF STUCCO BACK WHERE CONDUITS PENETRATE |
|
| 05/23/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ONE HOME 2) PLEASE RECALL FOR INSPECTION |